Twin-Spot Spacing Data

Mounting Height Spacing to Wall Between Units
2 x 21 Watt Tungsten Versions
2.5 Metres
3m
9m
4.0 Metres
4m
11m
6.0 Metres
3m
12m
8.0 Metres
3m
10m
2 x 20 Watt Tungsten Halogen Versions
2.5 Metres
5m
15m
4.0 Metres
6m
16m
6.0 Metres
5m
16m
8.0 Metres
4m
15m
2 x 55 Watt Tungsten Halogen Versions
8.0 Metres
8m
20m
10.0 Metres
8m
20m
 
Notes: These tables are based on the following factors: Light output ratios measured to BS5225 and lamp lumen outputs are from GE Lighting warm white lamps.
 
Requirements from BS5266/EN1838
Permanently Unobstructed Escape Routes
Require minimum of 0.2 lux along the centre line of the escape route, where there is a possibility of an obstruction occurring along the route then 1 lux minimum is required.
 
Undefined Open Areas
The minimum level of illumination required throughout the area is 0.5 lux excluding a half Metre border around the edge of the room which can be at a lower level.
 
Twin-Spot
All floodlighting units are fitted with two swivel mounted projectors each with a 30° beam spread.
To prevent glare, the luminaire should be mounted 30° above the line of sight.
All spacing are calculated to achieve 1 lux.

 

 

 

 

 

 

 

 

 