Easy to Install Emergency Conversion Kits for 12 Volt Lamps up to 50 Watts

SPEL's low voltage lighting train enables 12 volt Tungsten Halogen lamps to operate in the event of a power failure. The ability to feed the lighting train through ceiling aperture cut-out's of 60mm using Nicad versions and 85mm using sealed lead acid versions ensures easy installation.

The lighting train is available in Non-Maintained mode, where the lamp is only illuminated when the power fails and also Maintained mode, which is supplied with an integral transformer which operates the lamps both in mains healthy and in the event of a power failure.

The low voltage lighting trains features high quality, high temperature Nickel Cadmium batteries or 5 year sealed acid batteries and a silicone coated woven glass fibre sleeving ensuring the product complies with BS/EN60924. Maintained versions of the lighting train allow dimming of the Halogen lamps if required.

Nicad versions provide 3 hours duration in the emergency mode when using 20 Watt Halogen lamps and 1 hour duration when using 50 Watt Halogen lamps. All sealed lead acid version provide three hours duration in the emergency mode.

Nicad Version
Sealed Lead Acid Version
Ordering Codes & Information
Cat No
Battery Type
Emergency Output
Weight
R959/50/NM3

50W NM3 SLA

6 Volts
1.30Kg
R959/50/M3
50W M3 SLA
6 Volts
1.36Kg
R960/50/NM1*
50W NM1 Nicad
6 Volts
7.00Kg
R960/50/M1*
50W M1 Nicad
6 Volts
7.50Kg
 
Specification  
Mains Voltage: 230V 50Hz
Charge Current: 250mA
Charge Monitor: Red LED can be mounted on or adjacent to emergency luminaire
Batteries: 6V 4Ah (5 Cell) high temperature Nickel Cadmium or Yuasa 6V 4Ah sealed lead acid
Recharge: 18 Hours
Dimming: Phased dimming leading or lagging edge
Transformer: 50W electronic 230V 50Hz input/11.5V SELV output
Sleeving:
Silicone coated woven glass fibre (Fabric tested to BS476 pt 7 and Class 1 rating, temperature rating - 60°C to +250°C)
   
Unit Dimensions 
Nicad Versions: 800mm Overall Length
SLA Versions (Charger Box)::

Length 230mm x Width 74mm x Height 60mm

SLA Versions (Transformer Box): Length 230mm x Width 74mm x Height 60mm
SLA Versions (SLA Battery Box): Length 350mm x Width 74mm x Height 60mm
   
*Nicad versions give 1 hour of emergency back-up when using 50 Watt lamps and 3 hours of emergency back-up when using 20 Watt lamps
   
Cut-Out Dimensions
Nicad Versions: Fits through cut-outs of 60mm or above (Minimum ceiling void of 140mm required)
SLA Versions: Fits through cut-outs of 85mm or above (Minimum ceiling void of 230mm required)