An Attractive Range of LPCB Approved Detectors Featuring a Unique Remote Laser Test Unit for Easy Testing and Commissioning

Our attractive range of conventional detectors are tested and approved to EN54 parts 5 and 7 by the Loss Prevention Certification Board.

The photoelectric detector uses an enhanced chamber designed to be tolerant to long term build up of dust and other contaminants. Automatic drift compensation provides a high level of immunity to contamination and is combined with special signal processing, which factors tolerance to short lived transient currents. Both of these factors greatly reduce unwanted false alarms. The combination of smoke and heat detection in the combined optical smoke and heat detector, reduce unwanted false alarms further.

The fixed temperature heat detector only outputs and alarm condition when the ambient temperature reaches a fixed threshold of 58°C or 78°C. The rate of rise heat detector will provide an alarm condition when there is either a rapid change of temperature over a given period of time, or when a fixed threshold of 58°C is reached.

Our remote indicator is for local indication when a detector enters the alarm mode. It is commonly used when a detector is situated in areas such as a cupboard or ceiling void and the detector LED can not be seen. The square remote indicator is designed to fit into a standard 25mm pattress box and is fitted with a wide viewing angle light emitting diode.

Ordering Codes Specification
Cat No Description
Low profile stylish appearance
FPA-103 Photoelectric Smoke Detector
Hand-held laser test tool available
FPA-104 Combined Photoelectric/Thermal Detector
Low current consumption
FPA-105 58°C Fixed Temperature Heat Detector
Easy maintenance
FPA-106 Rate of Rise and Fixed Temperature Heat Detector
Extended 3-year warranty
FPA-107 78°C Fixed Temperature Heat Detector
Dust tolerant optical chamber design
FPA-108 Detector Base with Schottky Diode
Automatic drift compensation reduces false alarms
FPA-109 Laser Test Unit
Detector indicator operates from 5 to 30 Volts DC
FPA-014 Remote Detector Indicator c/w Text
 

The Laser Test Facility

Routine periodic testing, fault finding and testing during commissioning has traditionally involved physical access to installed detectors, which is often a time consuming procedure requiring step-ladders or access towers. Unique to the range of detectors is the remote laser test unit, which alleviates this arduous process. Here the service engineer simply has to direct the modulated laser beam at the detector LED, the detector will then respond and latch into alarm. The remote laser test unit is not suitable for first test commissioning as simulated smoke or heat must be used during this process.

 

 

 

 

 

Detector Technical Information    
Details
FPA-103
FPA-104
FPA-105/FPA-107
FPA-106
Operating Voltage:
14V-28V dc
14V-28V dc
14V-28V dc
14V-28V dc
Typical Stand-By Current @25°C
45µA at 24V dc
60µA at 24V dc
55µA/60µA at 24V dc
55µA at 24V dc
Maximum Alarm Current:
70mA at 28V dc
70mA at 28V dc
70mA at 28V dc
70mA at 28V dc
Operating Temperature Range:
-30°C to +70°C
-30°C to +70°C
-30°C to +70°C
-30°C to +70°C
Thermal Element Trigger Point:
N/A
+58°C
+58°C/+78°C
Rapid Change or +58°C
Maximum Humidity:
95% RH
95% RH
95% RH
95% RH
Colour Finish:
Approximates to RAL9016
Approximates to RAL9016
Approximates to RAL9016
Approximates to RAL9016
Case Material:
ABS
ABS
ABS
ABS
Compatible Base:
FPA-108
FPA-108
FPA-108
FPA-108
Diameter:
Ø 102mm
Ø 102mm
Ø 102mm
Ø 102mm
Detector Height (Including Base)
42mm
50mm
50mm
50mm
Weight:
75g
78g
70g
70g
Weight (Including Base):
120g
123g
115g
115g
Max Wire Gauge For Terminals
1.5mm²
1.5mm²
1.5mm²
1.5mm²

 

 

 

 

 

 

 

 

 

 