| Combining Seven modes of Detection and a Sounder all Within One Device |
![]() |
The multi-function detector is the key to all of our two-wire systems and offers seven different modes of detection and a sounder in one device. The mode of detection required is changed simply by configuring the DIL switch in the detector's electronics module. The multi-function detector can be supplied with or without an integral 90bDA sounder. Compact and easy to install, the multi-function detector is fully compliant with all European detector type specifications and is suitable for installations compliant with BS5839 Part1 1988. |
| Features | |
Three
smoke detection modes |
|
| Three heat detection modes (Two fixed, on rate of rise) | |
| Combination standard heat or smoke mode | |
| Can support up to 32 devices per zone Modes can be changed before and after installation | |
| Available with or without an integral 90dBA sounder | |
| Intelligent detector - Microprocessor controlled | |
| Continuous self-calibration | |
| Disposable optical chamber (No need for cleaning and can be economically replaced) | |
| Two high-performance optical smoke and heat sensors (Optical scatter smoke sensor, temperature sensor) | |
| Fully encapsulated electronics | |
|
|
Compact and easy to install |
| Ordering Codes |
| Cat No | Description |
| FPA-1010 | Combined Smoke/Heat Detector |
| FPA-1009 | Combined Smoke/Heat Detector/90dB Sounder |
| FPA-1016 | Detector/Sounder Head Removal Tool |
| FPA-1018 | Multi-function Device Replacement Chamber |
| Technical Information |
Operating Voltage: |
15 to 28 Volts dc (20 Volts dc Nominal) |
| Detector Operating Current: | Quiescent 60µA, Alarm 39mA |
| Sounder Operating Current: | Quiescent Nil, Alarm 39mA |
| Sounder Alarm Levels: | Normal Setting 90dBA, Low Setting 75dBA |
| Dimensions: | Ø 105mm x 32mm Height |
| Weight: | 270g |
| Modes of Detection |
Smoke
1 Used where ionisation detectors are normally fitted, especially
when the application has high ceilings or is susceptible to the risk of
free burning fires. |
Smoke
2 Used where optical detectors are normally fitted when there
is a risk of a smoldering fire and for escape routes. |
Smoke
3 Used where optical detectors are normally used in positions
exposed to brief concentrations of water vapour or smoke e.g. from a bathroom,
kettle etc. |
| Heat 1 Used where a standard rate of rise detector would normally be used. |
| Heat 2 Used where a standard 58°C fixed temperature detector would normally be fitted e.g. commercial kitchens. |
| Heat 3 Used where a standard 90°C fixed temperature detector would normally be fitted e.g. boiler rooms. |
| Smoke 2/Heat 2 A Combination of smoke 2 and heat 2 will trigger from either a smoke or heat source. |