A Comprehensive Range of Break Glass Call Points to Suit Most Applications

Our surface or flush mounted break glass call points meet the requirements of EN54 part 11 and are certified to BS5839 part 2 by the Loss Prevention Certification Board.

We produce a range of break glass call points in a variety of colours for installations with specific requirements.

Please refer to our sales team for details.

Features
Normally open contacts with 470R series monitoring resistor
A test key is supplied with each unit
An unlimited number of call points can be connected to the panel
A range of custom call points are available
Ordering Codes
Cat No Description
FPA-006 Surface Mounted Call Point
FPA-007 Flush Mounted Call Point
FPA-034 IP55 Surface Mounted Call Point
FPA-035 IP65 Surface Mounted Call Point
FPA-036 Replacement Glasses (Pack of 5)
FPA-059 Resettable Flag Indicating Call Point
FPA-081 Protective Cover
Suffix /WH for white, /BU for blue, /GN for green, /YE for yellow call points
Dimensions  
FPA-006: 87mm x 87mm x 52mm
FPA-007: 87mm x 87mm x 50mm
FPA-034/035: 124mm x 124mm x 60mm
Specification
Max Contact Resistance: 150 Milliohms
Max Contact Rating: 3 Amps
Min Recommended Voltage: 12V ac/dc
Resistor Wattage: 1W (2.5W for IP65 Version)
Resistor Ohmic Value: 470 Ohms
Operating Temp Range: -30°C to 70V°C
Frequency: 45/65Hz

 

 

 

 

 

 

 