LIGHTING REQUIREMENTS
When luminaires have been sited to cover the location above, additional luminaires may be required to ensure minimum lighting levels are
achieved
We provide spacing tables for this purpose. Spacing tables advise how far to locate the first luminaire, then how far apart other luminaires
should be located for a given mounting height. Installation to the spacings will ensure the lighting levels will be achieved
 
Escape route corridors etc: 1 lux minimum on the centre line of the escape route
Open Areas: 0.5 lux minimum in the central core to within 0.5m of the walls
Exit signs: Signs should apply to the European Signs Directive and be either back illuminated or have an emergency luminaire within 2m
of horizontal height. Signs should be of the same format throughout the building