| Central Battery Cubicles for Emergency Lighting Systems |
![]() |
Powerfaze central battery systems are manufactured to the highest standards to provide long, trouble-free service and can be specified with a range of battery types. The cubicles are manufactured from sheet steel and use lockable, lift-off covers, which provide excellent access to both charger and battery compartments during installation and maintenance. A choice of load capacities in non-maintained, AC/DC maintained and floating DC/DC maintained systems are available in 24, 50, 100 Volts. |
| Ordering Codes & Information |
Maintained
Models |
Non-Maintained
Models |
Voltage |
Duration |
Watts |
Cabinet |
PWF24/M3/420/AV/LV/S |
PWF24/NM3/420/AV/LV/S |
24V |
3 Hours |
420 |
1/A |
PWF24/M3/545/AV/LV/S |
PWF24/NM3/545/AV/LV/S |
24V |
3 Hours |
545 |
1/B |
PWF24/M3/635/AV/LV/S |
PWF24/NM3/635/AV/LV/S |
24V |
3 Hours |
635 |
1/B |
PWF24/M3/780/AV/LV/S |
PWF24/NM3/780/AV/LV/S |
24V |
3 Hours |
780 |
1/C |
PWF50/M3/270/AV/LV/S |
PWF50/NM3/270/AV/LV/S |
50V |
3 Hours |
270 |
1/A |
PWF50/M3/380/AV/LV/S |
PWF50/NM3/380/AV/LV/S |
50V |
3 Hours |
380 |
1/A |
PWF50/M3/600/AV/LV/S |
PWF50/NM3/600/AV/LV/S |
50V |
3 Hours |
600 |
1/A |
PWF50/M3/840/AV/LV/S |
PWF50/NM3/840/AV/LV/S |
50V |
3 Hours |
840 |
1/C |
PWF50/M3/1090/AV/LV/S |
PWF50/NM3/1090/AV/LV/S |
50V |
3 Hours |
1090 |
2 |
PWF50/M3/1270/AV/LV/S |
PWF50/NM3/1270/AV/LV/S |
50V |
3 Hours |
1270 |
2 |
PWF50/M3/1560/AV/LV/S |
PWF50/NM3/1560/AV/LV/S |
50V |
3 Hours |
1560 |
2 |
PWF50/M3/1960/AV/LV/S |
PWF50/NM3/1960/AV/LV/S |
50V |
3 Hours |
1960 |
3 |
PWF110/M3/610/AV/LV/S |
PWF110/NM3/610/AV/LV/S |
110V |
3 Hours |
610 |
2/C |
PWF110/M3/870/AV/LV/S |
PWF110/NM3/870/AV/LV/S |
110V |
3 Hours |
870 |
2/C |
PWF110/M3/1350/AV/LV/S |
PWF110/NM3/1350/AV/LV/S |
110V |
3 Hours |
1350 |
2/C |
PWF110/M3/1900/AV/LV/S |
PWF110/NM3/1900/AV/LV/S |
110V |
3 Hours |
1900 |
3 |
PWF110/M3/2450/AV/LV/S |
PWF110/NM3/2450/AV/LV/S |
110V |
3 Hours |
2450 |
3 |
PWF110/M3/2850/AV/LV/S |
PWF110/NM3/2850/AV/LV/S |
110V |
3 Hours |
2850 |
4 |
PWF110/M3/3500/AV/LV/S |
PWF110/NM3/3500/AV/LV/S |
110V |
3 Hours |
3500 |
4 |
| Options: |
| Replace # with quantity of outputs required. |
/BS
BS764 Contactor; /LVD Low Voltage Disconnect; /CA Common Alarm
Relay (V/F Contact); DM Digital Ammeter/Voltimeter; /EF Earth
Fault Monitor; /ET Engineers Test Key; /FA Fire Alarm Relay;
/HL High/Low Volts Monitor; /MI MCB on Mains Input (Single Pole);
/MM MCB on Maintained Circuit (Single Pole); /MR1 Maintained
Control Relay (Max 1500 Watts); /MR2 Maintained Control Relay
(Max 3500 Watts); /NW1 Night Watchman's Switch (Max 1500 Watts); /NW2
Night Watchman's Switch (Max 3500 Watts); /PF Phase Failure Relays;
/TS Solar Dial Time Switch; /RA Remote Alarm Unit; /SR
Sub-Circuit Relay; /FPL Flat Plate Lead Acid Batteries; /PLA
Planté Lead Acid Batteries; /NCA Nickel Cadmium Alkaline Batteries;
/#XD1 Double-Pole Fused Output (Max 32
Amps); /#XD2 Double-Pole Fused Output
(Max 63 Amps). |
| Specification |
| Input Voltage |
220/240
Volts 50Hz single phase or 380/415 Volts 50Hz three phase with phase failure
detection relays fitted. |
| Output |
| 24 Volts, 50 Volts or 110 Volts |
| Charger |
Thyristor
controlled constant Voltage type with electronic current limit and optional
boost facility. Protected against short circuit, low battery Voltage and also
reverse battery connection. |
| Meters |
| Moving coil charge Ammeter and battery Voltmeter. |
| Indicators |
| Mains healthy neon and charge fail LED. |
| Protection |
HRC
fuses to the input, charger and output. Low Voltage disconnect on sealed lead
acid type batteries. |
| Enclosure |
| Sheet steel finished in grey RAL-7032 |
| Recharge Time |
| Charges are rated to give 80% recharge within 14 hours and full recharge within 24 hours. |
| Minimum Battery Voltage |
The
battery Voltage at the end of a rated discharge shall not be less than 85%
of the nominal system Voltage as defined in BS5266. |
| Fuses |
| Industrial HRC complying with the general requirements of BS88 Part 2; 1975. |
| Contactors |
| To the relevant requirements of BS5424 as standard but BS764 types available on request. |
| Transformers |
Double
wound with either bobbin or earth screen, complying generally with the requirements
BS171. |
| Health & Safety |
When
lead acid and Nickel Cadmium wet cells are charged, they emit a potentially
explosive mixture of Oxygen and Hydrogen. Adequate ventilation when installing
equipment in confined areas is essential. A battery is electrically live at
all times and can not be isolated in the conventional sense. Therefore, precautions
restricting unauthorised access to battery rooms and cabinets should be undertaken. |
| Battery Options |
Powerfaze
central battery units are supplied with 10 year life sealed lead acid batteries
as standard. Descriptions of battery options offering a variety of costs,
service life and maintenance required are detailed as follows: |
| 10 Year Life Sealed Lead Acid |
Valve
regulated lead acid batteries are the most popular choice for central battery
systems as they are maintenance-free and have an expected service life of
10 years. The interior construction immobilises the acid within a sponge like
material and the electrolyte remains throughout the charge and discharge cycles.
There is no loss through gassing during the life of the battery as the cells
are completely sealed. |
| Flat Plate Lead Acid |
Low
antimony pasted plated cells are housed within a translucent plastic case,
which ensures ease of checking electrolyte levels. The cells have a low internal
resistance, which result in good regulation, especially at higher rates of
discharge. A large electrolyte reservoir enables longer periods between topping
up. This type of cell has a reasonable tolerance to neglect and has a service
life between 12 and 15 years. |
| Planté Lead Acid |
There
high performance cells offer ultra reliable trouble-free service when well
maintained. The clear cell casing enable the electrolyte levels to be checked
easily and a large electrolyte reservoir limits maintenance requirements.
The cells retain 100% capacity throughout their design life and give excellent
performance at high or low levels of discharge. This type of cell has a service
life up to 25 years. |
| Nickel Cadmium Alkaline |
These
cells are extremely robust and will tolerate arduous operating conditions.
The cells have translucent cases to enable the electrolyte level to be checked
easily. Deep discharge has no adverse effect on the cell capacity and unlike
lead acid cells, they can be left in a discharged condition without incurring
damage. This type of cell has a service life up to 25 years. |